A Saftey "One-stop" General Compensation Technique

DPS-H separate compensation

  • No harmonic is generated, no harmonic is amplified and the odd harmonic orders lower than 13th can be filtered.

Stepless adjustment

  •  DPS-H can realize dynamic stepless adjustment without over compensation and short-compensation

Modularized product design

  •  DPS-H adopts modular product design
    and cabinet installation.
  • It features convenient engineering design
    and installation

Power factor, Three-phase unbalanced and Loworder harmonic synchronization control

  • Mainly compensate power factor and threephase unbalance
  • Support low-order (3, 5, 7, 9, 11 orders) small capacity (50% rated power) harmonic compensation

Resonance avoidance

  •  DPS-H is a current source device which avoids resonance phenomena in mechanism

Multiple compensation applications

  • DPS-H separate compensation
  • DPS-H separate compensation

DPF-H Technical specifications

Shany-tech DPS-H 30/50/100KvarItem
380V(-40% ~ +20%
228V ~ 456V
Voltage of rated AC input lineSystem
parameters
Mains frequencyMains frequency
UnlimitedParallel operation
150/5 ~ 10,000/5CT setting
3P3W, 3P4WNetwork configuration
≥97%Eficiency
Power lossesPower losses
3-levelTopology designCharacteristics
30/50/100KvarRated compensation capacity
< 15msResponse time
-1 to 1, capacitive to inductive
continuously adjustable
Operation range
Smart air coolingCooling air requirement
<65dbNoise level
RS485 CANCommunication interfaceCommunication capacity
Modbus RTUCommunication protocol
YesAlarm events
LCD monitor/HMI centralized
monitor (optional)
Monitoring
Wall / Rack/CabinetMounting typePhysical aspects
Back (for module);
Top or bottom(for cabinet)
Cable entry
same size as DPSDimensions
21KG 30Kavar, 35KG 50Kvar, 100Kvar 48KGWeight
RAL7035Color
1,500m/derating up to 4,000m, 1% / 100mAltitudeEnvironmental conditions
-10~ 40(°C)Ambient temperature
5%~95%, non-condensingRelative humidity
IP20Protection class

DPS-H mode definition

DPS-H function comparison

Advanced Var Generator (DPS-H)Var GeneratorGeneral dynamic reactive power compensation (SVC)ItemCategory
AvailableAvailableSpecial designHarmonic controlHarmonic control function
3, 5, 7, 9, 11 (orders)Single order,
normally 3rd order
Compensation range
Dynamic real-time
compensation, stable
and reliable
Dynamic real-time
compensation, stable
and reliable
Common easily
influenced by system
fluctuation
ReliabilityReactive compensation function
-1~1-1~1Normally 0.6~1Compensation range
AvailableAvailableSpecial DesignPhase by Phase
Compensation
Imbalance compensation function
AvailableAvailableUnavailableImbalance
compensation
AvailableAvailableUnavailableActive imbalance
compensation
Dynamic real-time compensation, increase
a harmonic compensation function lower than 13th order
Dynamic real-time compensationCompensation capacity cannot be adjusted continuously, which makes it difficult to reach complete equilibrium with reactive system, and easy leading to over compersation and short-compersationCompensation modeKey feature
< 5ms< 5ms> 10msResponse time
The compensation capacity of DPS installed capacity.The compensation capacity of SVG is installed capacity.The installed capacity of
traditional compensation device is usually more than actual capacity
Capacity characteristic
The DPS floor space is always 50% of other reactive compensation type which has same capacity, even smaller.The SVG floor space is always 50% of other reactive compensation type which has same capacity, even smaller.LargeSpace

Operating principle

 DPS-H Advanced Generator conducts real-time monitoring to load current through external Current Transformer (CT) and detects reactive components and harmonic from load current through the calculation of internal DSP, then transmits PWM signal to internal IGBT. Conforming reactive current and low-order harmonic Acurrent are generated by inverter with control settings to achieve reactive compensation and control harmonic.

DPS-H operating principle diagram

DPS-H compensate non-linear capacitive loads

 SHANY-TECH DPS-H compensate non-linear inductive loads